Logo Munk GmbH
Product Enquiry Form

Thyristor Technology OWA

Application:

Degreasing, Zinc Coating, Chrome processes, High-current Processes

Product Description:

The robust Rectifiers in Thyristor Technology in water/oil cooling are designed for reliable operation in the harshest environments. All critical power components are completely submerged in oil so the best protection from the environment is guaranteed. The complete power unit is integrated in a plain sheet tank filled with insulating oil. The internal heat loss is completely discharged via the customer-provided cooling water by means of a circulation pump and an oil-water-heat exchanger. This concept provides an outstanding basis for energy-efficient approaches.

Due to the high water inlet temperature of up to 45 °C a return temperature of up to approximately 60-65 °C would be possible. With the MUNK oil water cooled Rectifiers waste heat can be sustainably used.

Our Thyristor Technology is also available in air-cooling, water-cooling and oil-cooling.

Block diagram / Functional Description:

Depending on the process capacity adjustment is achieved on the mains side (1) via transformers. On the secondary side (low voltage side) a silicon diode is used which takes over rectification. Regarding pole changing processes an anti-parallel Thyristor assembly is used on the secondary side (2) enabling a wear-free polarity change.

Customer Benefits:

The robust Thyristor-controlled Rectifiers in oil/water cooling is preferably used for output ranges ≥ 3000 A - 15000 A. Due to the compact design and the high protection grade (IP 54) an installation in direct proximity of the process is possible. Oil/Water cooled DC Power Supplies in Thyristor Technology are equipped with a sustainable heat recovery system to reduce energy costs.

Technical Data:

Mains Voltage:3 x 400 V, 50 Hz + N + PE
Output Current:> 1000 A - 15000 A
Output Voltage:6 V - 150 V
Ripple:approx. 5 % full range
Duty Factor:100 % (24/7)
Efficiency:80 % - 93 %
Ambient Temperature:+ 35 °C, > 40 °C (Option)
Protection Grade:IP 54 tank / IP 23 cover

Drawing:

The Thyristor-controlled rectifiers in oil/water cooling are available in the following tank sizes:

(Dimensions in mm)

TypWidthDepthHeightOil requirement
F18104901120160 kg
F29505701210210 kg
F311505801320290 kg
F412706101620440 kg
F513306701620460 kg
F613707101570480 kg
F714307701590500 kg
F815408001590580 kg
F915808801640660 kg
F10170010001640710 kg
F11205011301740930 kg
F122150118018901150 kg
F131920161020601850 kg
F142480148021702750 kg
F152600160021702900 kg
F162700170021702960 kg
F172800210021704100 kg
F182950210024204830 kg

Interfaces:

Digital high/low operating commands
Analog Voltage Values 0-10 VDC
Option: 4..20 mA, Profibus DP, PROFINET, etc.

Product Enquiry Form